AW103IM
Wireless Addressable Input Interface Unit
Wireless addressable input interface unit is designed to interface devices like wireless detectors/MCP with the addressable Fire alarm control panel. It consists of wireless receiver that accepts signal from wireless detectors/MCP and communicates to the fire alarm control panel along with alarm status like pre-alarm, alarm, contamination, low battery with device ID. This device is allocated with a unique ID, which facilitates their identification and control from the panel. Airlight interface units are connected to SLC and responds to regular polls to the panel.
Hybrid system
(Wireless + Wired)
Exclusive Features
Technical Summary
Exclusive Features
- Soft addressing
- Dual bi-colour LED indication for 360° viewing angle
- Easy to maintain/service
- Used to integrate wired and wireless system
- Low profile elegant design
Technical Summary
Electrical Specifications
Operating voltage : 17-27V DC
SLC Loop current : 8 mA
Carrier Frequency : 433.92Mhz
Indications
Normal : Red LED (Blinks during scan)
Alarm : Red LED (Blinks during signal reception)
General Specifications
Operating temperature : 0ºC to 49ºC
Storage temperature :10ºC to 50ºC
Humidity : 0-95% RH (Non-condensing)
Color : White
Compatibility : ALPA2XV1 Protocol
Housing : Polycarbonate
Dimensions(DiaxH)
Without Base : 100x30mm
With Base : 100x42mm
Weight
Without Base : 62g
With Base : 102g
others in Addressable series
Output Interface Unit