AL-FAPATBCP-101L
control panel for addressable automatic fire detection, automated voice alarm , public address and
talkback system
This control panel serves as a centralized unit, providing a wide range of functionalities, as required to meet NBC 2016 including
Automatic Fire Detection And Manually Operated Fire Alarm Using Voice Alarm:
Manually operated electronic fire alarms: ( MOEFA )If someone sees a fire, they can press a button to start a voice alarm. This is a message that says where the fire is.
Example of a voice alarm: “Attention please, fire alarm reported from automatic smoke detector of seventh floor electrical room, .” This helps both the people inside and the security or support personnel to rush to take appropriate action.
Automatic fire detection:
Besides the alarms people can trigger, there are also Automatic fire detectors that can sense smoke and heat. These detectors are put in places as required. They automatically activate voice alarms when they sense a fire.
PA System
The control panel features an Interactive Touchscreen controlled TFT Display, designed to be user-friendly for clear indications, easy navigation, and controls. Users have the flexibility to choose between activating individual speakers, required speakers, speakers within specific zones, or all speakers, using the intuitive touch screen display.
Talkback System
A crucial component of this system is the Talkback speaker, which enhances the usability of the PA speaker system. Initiating a call from the Talkback speaker’s call button or through the control panel’s display, along with identification and location information, establishes two-way communication once acknowledged. Similarly, calls can be made from control panel to targeted talkback units for communication. Furthermore, addressable voice call points and complementing addressable speakers can also serve as Talkback speakers.
Automatic fire emergency lighting:
Fires can make the normal lights go off. So, having special lights along escape routes is important. These lights turn on automatically during fires. They make sure people can see where to go
Electrical specifications
- Primary Power: 220V±10%AC
- Standby Power: Control panel have build in charger also it as provision to accommodate 12v, 18Ah SMF Battery(2 No’s)
- No. of Loop: 1
- Total devices per loop: Each loop has addressable capability up to 127 nos. each loop is capable to connect and operate loop powered speaker devices. Speaker is high current device hence each loop can drive up to 2000mA based on power requirement; device count shall be limited accordingly
- Maximum Signal Loop Current: 2000mA
- Loop Resistance :40 ohms
- Wiring :2core cable
- Wiring Type :Class A/ Class B Style
Control panel for Addressable public address and Addressable Talkback speaker system : This control panel has been specifically designed for addressing fire emergencies through a Public Address and Talkback speaker system. It aligns with the requirements set out in NBC 2016, including Addressable Public Address Systems, Addressable Talkback speaker systems, Addressable Fire drill systems, and Addressable voice evacuation systems.
Integrity and optimal use of cabling: The addressable speakers and Talkback speakers integrated with this control panel utilize loop power and a 2-wire setup. The control panel adheres to fire safety standards, ensuring the integrity of wiring connectivity, device connectivity, and overall functionality through automatic health checks.
Service Engineer friendly feature : To ensure reliability, the control panel designed using minimal electronic components, thereby reducing the likelihood of failure . The control panel circuits are made in to modular construction. These plug in modules helps service personnel to attend rectification processes by just replacing defective modules with in no time.
Power supply for the System:The control panel and devices operate on a 24- volt power supply. The control panel is designed to accommodate both external and built-in power supply options.
External Power Supply: The control panel has a provision to directly connect a 24-volt external power supply. This supply can be sourced from the nearest fire alarm panel or any other compatible source. The objective is to reduce OEM dependence, save space, and minimize costs.
Built-in Power Supply: The control panel is also equipped with a built-in power supply unit capable of converting 230 volts AC supply to 24 volts DC. Additionally, it features a built-in battery charger and ample space to accommodate two 12-volt batteries. Users can choose from various capacities ranging from 7 AH to 18 AH, depending on their power requirements. This setup ensures uninterrupted power supply during emergencies and aids in system reliability.
others in series
Model No: ALFACP101L
Model No: ALPACP101L
Model No: ALTBCP101L
Model No: ALPATBCP101L