ALFCCP-PATB-104
Addressable Automatic Fire command and Control Panel (PA+TB)-4 Loop
Addressable automatic fire command and control panel designed to deliver a NBC 2016 specified functional requirements such as public address and talkback system. This compact control unit works on android computer having very less hardware and less vulnerable to hardware failure. Easy to understand and operate the system especially during emergency
PA & talkback products
Exclusive Features
Technical Summary
Exclusive Features
- Works on Android platform
- 2 level password protection
- Built with minimal hardware to reduce failure rate, made compact and aesthetically designed
- Interactive 7” TFT display with touch screen control
- Onsite configuration can be done directly through panel display
Technical Summary
Electrical Specifications
Primary Power: 220V±10%AC
Standby Power: Control Panel Have Built In Charger Also It Has Provision To Accommodate 12V,18Ah SMF Battery (2 No’s)
No of loop: 1
Total devices per loop: Each loop has addressable capability up to 127 nos. each loop is capable to connect and operate loop powered speaker devices. Speaker is high current device hence each loop can drive up to 2000mA based on power requirement; device count shall be limited accordingly.
Loop Current: 2000 mA
Loop Resistance: 40 Ohms
Wiring: 2 core cable
Wiring type: Class A/ Class B Style 4
Wiring: 2 core cable
Wiring type: Class A/ Class B Style 4
Finish
Enclosure Dimensions(HxWxD): 560x400X127 mm
Housing Material: 16 Gauge Cold Rolled sheet
BackBox: Black Matte