ALFAPACP101
ADDRESSABLE INTEGRATED CONTROL PANEL FOR FIRE ALARM AND PUBLIC ADDRESS SYSTEM-1LOOP
This Addressable integrated Automatic Fire detection, Voice Evacuation, Public Address system control panel is designed to deliver integrated control and indicating functions of Fire, Public Address as prescribed in an NBC 2016 code for fire and life safety.
As per NBC2016, buildings shall have an Automated system by Detecting fire automatically and warning the occupants automatically using voice notification (English/ vernacular language) to safeguard their life from fire. It shall have one-way communication using a Public Address system.
ABOUT FIRE DETECTION SYSTEM FUNCTION
Addressable intelligent automatic smoke/ heat sensors can be connected to gather the data of smoke/ temperature levels from the protected areas. When the data contains the presence of smoke or abnormal temperature, the control panel signals Voice notification using the English language to the targeted location through Public Address system speakers. It also signals to trip Electromechanical equipment using control modules. The control panel has a built-in Android computer, it has a large display and interactive touch screen. The display indicates a zone of fire and the exact location of the fire.
ABOUT PUBLIC ADDRESS SYSTEM FUNCTION
This Addressable Public Address system function is designed to make targeted announcements to the occupants. The dashboard has facilities to control individual, zone wise and all speakers based on requirements. Each and every speaker has a unique ID with a digital speaker driver board. This control panel is mainly designed for the fire safety system, therefore each and every speaker unit are continuously scanned for fault monitoring. In case any speaker does not report during the scan will be reported to the control panel for fault alert alarm.
ABOUT FAULT MONITORING
The Control panel is designed to ensure all the components of the system and its wiring is active. This self-diagnostic feature continuously scans (electrically supervise), When any fire detection device or speaker unit goes out of the circuit, the front panel display indicates the missing device ID and its location. In the case of a short circuit in the wiring, the system automatically diagnoses its location and isolates defective circuits, and keeps other circuits functional with the use of a short circuit isolator.
POWER BACKUP
This control panel has a built-in battery charger and space to place the backup batteries for uninterrupted operation.
CONFIGURATIONS
Based on fire alarm requirements, relevant device activation can be configured using a front panel display. No external laptop or dongle is required.
PASSWORD PROTECTION
2 level password protection is provided
ABOUT WIRING
The system utilizes only 2 core cables. The audio signal, control signal, and power are carried in one 2 core cable.
The Control panel has a blue tooth, Wi-Fi, SIM card, additional space for a memory card. It can be connected to the internet to play music directly. It has a feature of an event log.
fire alarm & pa products
- Networkable fire detection and fire alarm control panel-1Loop
- Networkable fire detection and fire alarm control panel-2Loop
- Networkable fire detection and fire alarm control panel-3Loop
- Networkable fire detection and fire alarm control panel-4Loop
- Networkable fire detection and fire alarm control panel-5Loop
- Networkable fire detection and fire alarm control panel-6Loop
- Android OS with touch screen control
- Graphic display available in “7”
- 2 Level Password protection
- Upto 1000 event logging capacity
What is a fire alarm panel or control panel?
It is the device that controls all the connected initiating devices (smoke detectors, manual call points, etc.) and notification devices(sirens, alarm sounder, etc.).
This fire control panel receives information from the connected devices and reports fire or fault based on the information communicated. The connected devices receive a power supply from the fire control panel equipment.
What are the different types of fire alarm panels?
Fire Control panels are either of type
- Conventional
- Addressable
Conventional Fire Alarm Panel:
This type of fire control panel indicates only the zone in the fire. The exact location cannot be determined from a conventional fire alarm panel or system. Conventional fire panels utilises LED as zone indicators.
Addressable Fire Alarm Panel:
This type of fire control panel indicates the exact location of the fire by identifying the location of the device in the alarm. Every device in an addressable fire alarm network is assigned with a unique ID that is taken as a reference to identify the device location.
others in series
Addressable Integrated Control Panel For Fire Alarm And Public Address System-2 Loop
Model No:ALFAPACP102
Addressable Integrated Control Panel For Fire Alarm And Public Address System-3 Loop
Model No:ALFAPACP103
Addressable Integrated Control Panel For Fire Alarm And Public Address System-4 Loop
Model No:ALFAPACP104
Addressable Integrated Control Panel For Fire Alarm And Public Address System-5 Loop
Model No:ALFAPACP105
Addressable Integrated Control Panel For Fire Alarm And Public Address System-6 Loop
Model No:ALFAPACP106