Addressable Duct Detector

AU101DSD

Addressable Intelligent Duct Smoke Detector

This Addressable Intelligent Duct Smoke detector is a networkable instrument that houses smoke sensor for monitoring the level of smoke in the air stream of duct work sections of the HV AC air handling system. Its unique feature is to provide the live smoke level to the control panel for real time monitoring purpose.
Exclusive Features
  • Soft addressing
  • Contamination alarm
  • Real time smoke info
  • Remote test facility from the panel
  • Remote sensitivity alteration from the pane
  • Electrical supervision
  • Insect-resistant screening
  • Address can be changed from the pane
  • Easy to maintain/service
  • Dual bi-color LED indication for 360° viewing angle
  • Transient voltage protection upto 2.4KV
  • Corrosion protection
Technical Summary

Electrical Specifications
Operating voltage : 17-27V DC
Quiescent current : 200uA
Alarm current : 1mA

Indications
Normal : Green LED(Blinks during scan)
Alarm : Red LED(Glows steady) 

General Specifications
Smoke sensitivity : 0.5 - 3.5 %obs/foot
Operating temperature : 0ºC to 49ºC
Storage temperature : 5ºC to 40ºC
Humidity : 0-95% RH(Non-condensing)
Color : White
Compatibility : AU101X Protocol
Detector Contact Clamp : Stainless steel
Housing Material : 16 Gauge Cold Rolled sheet
Detector Housing : Polycarbonate
Back Box : Black Matte
Front Cover : Acrylic sheet
 
Mechanical Specifications
Dimensions(LxBxD) : 155x150x150mm
Sampling Tube : 205mm
Exhausted Tube : 220mm
 
Weight
Without Detector : 1710g
With Detector : 1820g
Know More

What is a smoke detector and how does it work?

Smoke detector is a measuring instrument that measures the level of smoke in its surveillance. It will raise an alarm only when the level of smoke exceeds its pre-set upper limit/threshold values.

Photoelectric/Optical Smoke detector work on a common light scattering principle. Smoke detector contains a chamber that consists of a light emitter usually a LED and a light a sensitive device like a photodiode that receives all the light directly emitted by the LED.

When the smoke enters the chamber, the intensity of light received by the photodiode reduces due to density of smoke. If the intensity of received light drops below a pre-set threshold level, fire alarm is triggered confirming fire. 

Unit of measure for level of smoke is Obscuration/foot (Obs/ft).

Photoelectric smoke detectors are highly sensitive to visual particles of smoke and also respond quickly to smouldering fires.

Addressable smoke detectors are wired using 2*1.5 sqmm copper cables from control panel.

----Visit FAQ to know more

 

 